DNB2-32 Mini circuit breake
Application Range:
DNB2-32 mini circuit breaker is applicable to AC 50Hz/60Hz protection circuit of 230V rated voltage and maximum 32A rated current for overload and short-circuit protection. And it can also be applied for non-frequent switching of circuits in normal conditions, especially for lighting and distribution system.
This product complies with standard GB10963-1999 and IEC60898-1995.
Model and the explanation:
Main specs and technical parameters:

Main technical parameters:
3.1 Classification
3.1.1 Classified according to rated current:  6A¡¢10A¡¢16A¡¢20A¡¢25A¡¢32A six types in total
3.1.2 It's a two-pole breaker with one protected pole if classified according to pole number (1P+N)
3.1.3 The instantaneous release is of Type C. (5ln¡«10In)
3.2 Main technical parameters and indexes
3.2.1 Main technical parameters (see Table 1)
3.2.2 Rated short-circuit breaking capacity: 4500A
3.2.3 Mechanical and electrical life: operation for more than 4000 times 

Structural characteristics
4.1 The product is of small and compact structure, holding two poles - 1P+N within the 18mm width and with volume to only half of the two-pole DNB1 product. And it also has more favorable price-performance ratio than any other similar products.
4.2 Shell and some function parts of the products are made of plastics with highly fire-retardant, high-temperature and impact resistant property.
4.3 The product shall be installed with neutral lines connected, so as to prevent possible electric shock hazard due to incorrect wiring of neutral lines.
4.4 The product can be installed easily and in short time with application of guide rails.